I am not sure I agree, I would rather have one reliable, properly sized, tested/measured ground, then, unless in an in an emergency, a random selection of undersized, maybe good grounds, and let the electrical devices figure which one is best. IE, if a ground is thought to be not correct, then any additional backup grounds have to all be the same proper size, thinking you can "share" or combine grounds is unwise and asking for future problems.

"static straps", are primarily for grounding static charges, not grounds.





My point was not to have a bunch of undersize grounds. My point was its nothing wrong with adding a ground of the correct size even if you already have a ground of the correct size in whatever circuit you are working with. Hence the saying .....you can never have to many grounds. Ron




I believe I understand your overall point, but the problem I see is when one has multiple grounds, often for extra assurance/back-up/whatever, unless they are all sized for the largest possible current demand, when one of the redundant grounds becomes less effective (corrosion, intermittent, loose, disconnected in error, etc), the current will then seek another ground with less resistance, and IF that ground is undersize, issues arise. Therefore My concept is just to have a single "great" ground path, and if a problem with that ground arises, the effect is immediate and maybe very obvious, and likely in a single location. That's why having a "lot" of grounds is not a goal for me.