Aluminum Line or Copper Line or? for Oil System
#1808456
04/21/15 10:33 AM
04/21/15 10:33 AM
|
Joined: Jan 2003
Posts: 4,283 Danville, NH
Mopar_Mike
OP
master
|
OP
master
Joined: Jan 2003
Posts: 4,283
Danville, NH
|
Because of my set up, I need to run some sort of tubing for my external oil system. Braided hose/fittings just won't work. What do you guys recommend for tubing? aluminum, copper or other? Thanks.
RS23L7 4-Speed
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: Mopar_Mike]
#1808472
04/21/15 10:44 AM
04/21/15 10:44 AM
|
Joined: Jul 2010
Posts: 1,845 Tampa
DusterDave
top fuel
|
top fuel
Joined: Jul 2010
Posts: 1,845
Tampa
|
I sure wouldn't use copper. Copper can work harden from vibration, and eventually crack. I'd be leary of aluminum for the same reason. I'm thinking steel or stainless steel would be a better and safer option. The factory doesn't use copper or aluminum lines for transmission and brake lines for a reason.
Gone to the dark side with an LS3 powered '57 Chevy 210
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: B G Racing]
#1808492
04/21/15 11:13 AM
04/21/15 11:13 AM
|
Joined: Jan 2003
Posts: 4,283 Danville, NH
Mopar_Mike
OP
master
|
OP
master
Joined: Jan 2003
Posts: 4,283
Danville, NH
|
Thanks guys.. I am in such a corner with this set up. I have 67 Coronet with a factory V8 K-frame. I am running a 66 Hemi and using the shumacher (sp?) conversion mounts. I am also using a Milodon external single line oil system. My pick up runs straight out (aiming towards the wheel rather then to the front of the car) and there is just no room to run a 45 or 90 fitting in there. I thought I might run a hard line and be able to bend it to the angle I need to get it facing down toward the pan. But basically a hard line here would not be a good idea because of vibration and cracking?
RS23L7 4-Speed
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: B G Racing]
#1808493
04/21/15 11:13 AM
04/21/15 11:13 AM
|
Joined: Feb 2005
Posts: 20,174 PA.
pittsburghracer
"Little"John
|
"Little"John
Joined: Feb 2005
Posts: 20,174
PA.
|
Hard lines are a NO,No unless you have flexabile attaching sections.Hard lines can be used only if it is a short distance on fixed componant and not effected by vibration.Never use copper.Stainless is good for short runs but can crack with vibrations or movement especially at the connections. Bob hit this nail on the head, DO NOT USE HARD LINES.!!!! A line fractured at the fitting on my Daytona back in 2010 and gave me quite a ride.
1970 Duster Edelbrock headed 408 5.984@112.52 422 Indy headed small block 5.982@112.56 mph 9.42@138.27
Livin and lovin life one day at a time
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: pittsburghracer]
#1808508
04/21/15 11:34 AM
04/21/15 11:34 AM
|
Joined: Jun 2003
Posts: 52,972 Romeo MI
MR_P_BODY
Master
|
Master
Joined: Jun 2003
Posts: 52,972
Romeo MI
|
There is nothing wrong with hard line.. it just needs to be mounted right.. look at heavy equipment.. thats all steel line unless it goes past a moving part(like a bucket) then it gets hose.. but even the connection points are rigid .. on a car the factory puts steel all the way down the chassis for the fuel & brake lines but they use a hose to jump to parts that move(the engine)... its all about the mounting
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: Mopar_Mike]
#1808526
04/21/15 11:58 AM
04/21/15 11:58 AM
|
Joined: Jan 2003
Posts: 13,363 Marion, South Carolina [><]
an8sec70cuda
I Live Here
|
I Live Here
Joined: Jan 2003
Posts: 13,363
Marion, South Carolina [><]
|
Why not change your oil pump configuration? Use the Milodon pump w/ the external p/u that comes right off the pump towards the front of the car and then you can use a stock oil pump cover. Would give you more options and clearance.
CHIP '70 hemicuda, 575" Hemi, 727, Dana 60 '69 road runner, 440-6, 18 spline 4 speed, Dana 60 '71 Demon, 340, low gear 904, 8.75 '73 Chrysler New Yorker, 440, 727, 8.75 '90 Chevy 454SS Silverado, 476" BBC, TH400, 14 bolt '06 GMC 2500HD LBZ Duramax
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: an8sec70cuda]
#1808542
04/21/15 12:19 PM
04/21/15 12:19 PM
|
Joined: Jan 2003
Posts: 4,283 Danville, NH
Mopar_Mike
OP
master
|
OP
master
Joined: Jan 2003
Posts: 4,283
Danville, NH
|
yeah, I have thought of that too.. its all about the $$$ though.. If I can't do something with line then that is going to be my next step.
RS23L7 4-Speed
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: B G Racing]
#1808568
04/21/15 12:56 PM
04/21/15 12:56 PM
|
Joined: Jun 2003
Posts: 52,972 Romeo MI
MR_P_BODY
Master
|
Master
Joined: Jun 2003
Posts: 52,972
Romeo MI
|
Bob.. I was a heavy equip operator and wrench when I was in the Army.. I still have a track loader.. thats why I mentioned the heavy equip and also knowing that you have equip.. some guys dont check the attachment points for the lines and they end up vibrating and crack and yes if they crack it does tend to crack at a fitting
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: MR_P_BODY]
#1808589
04/21/15 01:28 PM
04/21/15 01:28 PM
|
Joined: Jan 2003
Posts: 16,376
dogdays
I Live Here
|
I Live Here
Joined: Jan 2003
Posts: 16,376
|
I'd stick with mild steel if you must run hard line. One thing for sure, solid line needs to be supported solidly. That means at the very minimum at both ends. If length is more than 6" or so, I'd support the middle or more points. You shouldn't be able to move the tubing when you're done.
There may be an easier way, as described above.
R.
Last edited by dogdays; 04/21/15 01:29 PM.
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: dogdays]
#1808594
04/21/15 01:41 PM
04/21/15 01:41 PM
|
Joined: Jan 2003
Posts: 4,283 Danville, NH
Mopar_Mike
OP
master
|
OP
master
Joined: Jan 2003
Posts: 4,283
Danville, NH
|
Well, what I think I can do is bend the tubing to make me the angle I need to drop down. I have a male AN -12 fitting coming out of the pick up. I was thinking of using 3/4" OD tubing, flaring it and then a sleeve with sleeve nut to attach to the fitting. Once the curve (probably 3-4 inch of hard line) is made I can sleeve and sleeve nut the other end of the hard line and run braided AN -12 hose to the bottom of the pan where there is an AN -12 90 degree. At the pick up, with 45 and 90 degree AN -12 fittings they not only don't fit (not enough room) the angle to the pan is wrong too.
RS23L7 4-Speed
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: Mopar_Mike]
#1808708
04/21/15 04:23 PM
04/21/15 04:23 PM
|
Joined: Jan 2011
Posts: 4,785 Utah and Alaska
astjp2
master
|
master
Joined: Jan 2011
Posts: 4,785
Utah and Alaska
|
Well aircraft vibrate like crap and use rigid aluminum lines at 1800 psi and stainless in the 3000+ psi range in a non moving environment, its all about the types of bends and the support it needs. Most lines need support if they are like 2 feet long, depending on the diameter. I went with stainless .080 wall tubing for my oil pickup, my fuel lines will .035, 321 stainless with JIC flares. Tim Some interesting reading for those of you who can read this dry stuff. https://www.faa.gov/regulations_policies...083-30_Ch07.pdf
Last edited by astjp2; 04/21/15 04:28 PM.
1941 Taylorcraft 1968 Charger 1994 Wrangler 1998 Wrangler 2008 Kia Rio 2017 Jetta
I didn't do 4 years and 9 months of Graduate School to be called Mister!
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: Mopar_Mike]
#1808787
04/21/15 06:12 PM
04/21/15 06:12 PM
|
Joined: Jan 2005
Posts: 866 Winnipeg ,Mb. CA.
chryco
super stock
|
super stock
Joined: Jan 2005
Posts: 866
Winnipeg ,Mb. CA.
|
If you have room for solid line,you'll have room for braided ????
Gas is fer washin' parts ....Alky`s fer drinkin' ...Nitro`s fer Racin'!
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: Mopar_Mike]
#1808859
04/21/15 07:57 PM
04/21/15 07:57 PM
|
Joined: Oct 2005
Posts: 8,872 Ontario, Canada
Stanton
Don't question me!
|
Don't question me!
Joined: Oct 2005
Posts: 8,872
Ontario, Canada
|
Milodon used to and still may make a aluminium line that connected to the pumps with the front pickup and went part way to the pan with a #12 AN hose for the final few inches and hook up.These were flared fitting and we found many leaked at the flare and the flare split from constant vibration.Most flared aluminium tubing is weak at the flare from streching the metal.If your going the flared route used the nut and flared collars that help support the flare on the tubing. I have and use one of those lines. They do use the collar and nut on them. I've had no leaks. However I find that ANY time you use a flared fitting you should wobble it as you're assembling and tightening it so that it seats in the sweet spot. This is particularly true with aluminum fittings as the aluminum is soft enough to bend/dent/etc while its being tightened but hasn't properly seated. Then it'll leak. Maybe these photos will help the OP - not a hemi but gives an idea of hose routing out the end of the pump.
|
|
|
Re: Aluminum Line or Copper Line or? for Oil System
[Re: Mopar_Mike]
#1809016
04/21/15 10:21 PM
04/21/15 10:21 PM
|
Joined: Jan 2011
Posts: 4,785 Utah and Alaska
astjp2
master
|
master
Joined: Jan 2011
Posts: 4,785
Utah and Alaska
|
I went with rigid stainless because it does not have the problem of moving and rubbing on things. Those braided lines are not supported to keep them from moving. Just an observation. Tim
1941 Taylorcraft 1968 Charger 1994 Wrangler 1998 Wrangler 2008 Kia Rio 2017 Jetta
I didn't do 4 years and 9 months of Graduate School to be called Mister!
|
|
|
|
|